March 16, 2011
Tecumseh Compressor Company
Indoor Condensing Units
Model: AWA2457ZXTXF BoM: 2B3264-1 R-404A 1.5 HP AIRCOOLED
Dimensions, inches Line Connection* Pumpdown Air Oil Ch Gr. Wt.
Model
L W H CH Suction Liquid
90 F 90%
SCFM Oz. Lbs.
AWA2457ZXTXF
25.0 33.5 19.5 14.7 7/8” S 3/8” S 16.46 lbs 1600 38.5 200
* F = Flare, S = Solder, RF or RS = Rotolock with Flare or Solder Connections, C = Compression Fitting
Ambient Temperatures
Evaporator T
80F 90F 100F 110F
°F PSIG BTUH Watts Cond T BTUH Watts Cond T BTUH Watts Cond T BTUH Watts Cond T
-40 11.9 1965 941 85 1501 879 94 --- --- --- --- --- ---
-35 15.0 2550 1027 86 1992 970 96 --- --- --- --- --- ---
-30 10.7 3263 1123 87 2608 1073 96 1946 1016 105 1285 955 114
-25 14.0 4040 1220 88 3295 1178 97 2564 1127 106 1813 1070 115
-20 17.1 4921 1320 89 4086 1288 98 3275 1246 107 2447 1193 116
-15 19.3 5882 1422 91 4955 1401 99 4032 1366 108 3137 1321 117
-10 24.5 6924 1525 93 5895 1515 101 4883 1490 110 3863 1452 118
-5 28.8 8059 1629 95 6932 1632 103 5797 1617 111 4743 1589 119
0 33.5 9323 1732 97 8037 1749 105 6814 1746 113 5591 1726 121
5 36.5 10537 1836 98 9195 1866 106 7897 1875 114 6556 1866 122
10 43.7 11976 1932 100 10462 1980 108 9028 2003 116 7615 2006 124
60 Hz Performance
Return gas temp. 40F, 5F sub-cooling